Skip to main content
Submitted by Anonymous (not verified) on Mon, 02/26/2024 - 09:09
2022 No https://www.ncbi.nlm.nih.gov/pmc/articles/PMC9395798/ Hou, Dandin North America Experimental Elementary (K-5) Ventilation rates Carbon Dioxide (CO2) COVID-19 Bayesian calibration Markov chain Monte carlo Ventilation rate School Carbon dioxide (CO2) The outdoor ventilation rate, CO2 generation rate, and occupancy level were identified as the top sensitive parameters for indoor CO2
levels. The occupancy schedule becomes critical when the CO2 data are limited, whereas a 15-min measurement interval could capture dynamic CO2 profiles well even without the occupancy information. Hourly CO2 recording should be avoided because it failed to capture peak values and
overestimated the ventilation rates. For the four primary school rooms, the calibrated ventilation rate with a 95% confidence level for fall condition is 1.96±0.31 ACH for Room #1 (165 m3 and 20 occupancies) with mechanical ventilation, and for the rest of the naturally ventilated rooms, it is 0.40±0.08 ACH for Room #2 (236 m3 and 21 occupancies), 0.30±0.04 or 0.79±0.06 ACH depending on occupancy schedules for Room #3 (236 m3
and 19 occupancies), 0.40±0.32,0.48±0.37,0.72±0.39 ACH for Room #4 (231 m3 and 8–9 occupancies) for three consecutive days.